Water
Allows a substantial pressure reduction in a single stage when the flow capacity is correctly selected.
Compressed air
Permits a large pressure drop, but the flow velocity and the noise level have to be checked.
Steam
With a large pressure drop, the rise in velocity, possible erosion and the service life of the control unit must be taken into account.
Recommended P1/P2 ratio
In practice it is recommended not to exceed 4:1. For a larger drop, staged pressure reduction is considered.
Kv selection
The minimum flow rate should be at about 40 % of travel and the maximum at about 60 % of the valve travel.