Skip to content

Institut Mihajlo Pupin · turbine governing and protection

ARS-TSControl · TCimp steam turbine governing and protection

ARS-TSControlTCimpAtlas-BPCSIL3API-670

A steam turbine governing and protection system on Atlas Max-RTL® controllers with direct pulse outputs to the control valves. The TCimp electro-hydraulic block trips the turbine on the “2 out of 3” principle and is certified for SIL3.

  • SIL3TCimp · IEC 61508, DEKRA certificate, 2022
  • 10ms — the governor’s critical function cycle
  • 348.5MW — the largest turbine in the references
  • 24h — automatic test of the protection channels
A 16 MW steam turbine, MSK Kikinda · an institute reference site
A 16 MW steam turbine, MSK Kikinda · an institute reference site

How it works · ARS-TSControl · TCimp

Speed, valves, “2 out of 3” protection.

  1. Multi-channel measurement: inductive probes read the gear on the rotor and give pulse trains.

  2. Speed, power and live-steam pressure governors, limiters, rotor thermal stress calculation. Logic in 30 ms, critical functions in 10 ms.

  3. New start-up and shut-down sequences; the turbine auxiliaries by functional groups.

  4. Three protection channels drive the three solenoid valves of TCimp. Two active — the oil supply is cut and the hydraulic drives close the valves. One — an alarm only; the turbine keeps running.

  5. Every 24 hours the channels are tested one at a time without affecting the other two, as API-670 requires.

Speed measurement

System components

  • ARS-TSControl

    Turbine governors and limiters on Atlas Max-RTL®, two-level redundancy, a function block library.

  • TCimp

    The “2 out of 3” block: 0.05–0.1 s response, up to 720 l/min, IP65, ATEX on request; API-670, API-612, API-611.

  • Atlas-BPC

    Turbine speed monitoring modules.

  • Overspeed protection

    Independent electronic protection — Atlas-NBZ or JAQUET FT300, per project.

  • Turbine simulator

    A software version for developing the algorithms and a hardware one for testing the cabinet.

  • IMP-PHA

    A mobile hydraulic unit for testing governor hydraulics in the factory and on site.

Protocols and standards

  • SIL3 · IEC 61508
  • API-670
  • API-612
  • API-611
  • “2 out of 3” — protection
  • “2 out of 2” — governing
  • ENTSO-E P1

Where it is used

  • TPP and CHP steam turbinesCondensing and district-heating, 65–348.5 MW.
  • Industrial turbinesCompressor drives, 11.9–16 MW.
  • Rotating machine protectionTCimp — for steam, hydro and gas turbines and in the process industry.

Institut Mihajlo Pupin

The institute’s experience

  1. 2023
    CHP Novi Sad, TA1A 135 MW district-heating turbine (165 MW max)
  2. 2019
    MSK KikindaAn 11.9 MW back-pressure turbine — air compressor drive
  3. 2016
    MSK KikindaA 16 MW condensing turbine
  4. 2016
    CHP Novi Sad, TA2A 110 MW district-heating turbine
  5. 2015
    TPP Kostolac B1A 348.5 MW condensing turbine
  6. 2011
    TPP Kostolac B2A 348.5 MW condensing turbine
  7. 2011
    TPP Kolubara A3A 65 MW condensing turbine
  8. 2010–2011
    TPP Nikola Tesla A1 and A2210 MW K-200 turbines; the response meets ENTSO-E P1 (2012 test)

Solution selection

Inquiry: ARS-TSControl · TCimp

Describe the site and the task. Trinone Group selects a solution on the institute’s systems together with the group members’ equipment and prepares the proposal and the documentation.

  • The site and the task
  • System and equipment scope
  • Proposal and documentation
Request a solution

QuestionnaireFill in onlineFill in by hand

Leaflet · Institut Mihajlo Pupin ARS-TSControl · ARS-THControl 40 pages · EN
Download PDF

← → turn · Esc close

Leaflet · Institut Mihajlo Pupin TCimp · “2 out of 3” trip block 6 pages · EN
Download PDF

← → turn · Esc close

Certificate · Institut Mihajlo Pupin TCimp · SIL3 certificate 2 pages · EN
Download PDF

← → turn · click to zoom · Esc close

Reference list · Institut Mihajlo Pupin ARS-TSControl · reference list 2 pages · EN
Download PDF

← → turn · click to zoom · Esc close

Case study · Institut Mihajlo Pupin ARS-TSControl 210 MW · case study 2 pages · EN
Download PDF

← → turn · click to zoom · Esc close