Installation and operation
The regulator must operate on clean gas. A strainer is installed upstream of the regulator. Installation is horizontal; the standard flow direction is right to left.
GasTeh · G100 · Series 110
Type 112Small and pilot regulators
Reduces the inlet gas pressure and automatically maintains the specified outlet pressure. The required version is selected according to the process medium, flow rate, and inlet and outlet pressure ranges.
In the printed catalogpp. 10–11Manufacturer’s data
Manufacturer — GasTeh
The regulator must operate on clean gas. A strainer is installed upstream of the regulator. Installation is horizontal; the standard flow direction is right to left.
Gas pressure regulator type 112 of series 110 maintains a stable outlet pressure in natural gas, propane-butane, air, nitrogen and other compatible technical gas systems.
| Body | AlSi |
|---|---|
| Seat | CW614N (CuZn40) |
| Seat plug | CW614N (CuZn40) |
| Spring / setting spring | carbon spring steel |
| Adjusting screw | CW614N (CuZn40) |
| Diaphragms 7a / 7b | Effbe |
| Cap | plastic |
| G1 | G 1/4″ or G 1/2″ |
|---|---|
| G2 | G 1/4″, G 1/2″ or G 3/4″ |
| A / B / C | 100 / 363 / 189 mm |
| p₂ range | 1-10 bar |
| RG / ZG | 5 / 10 |
Equipment selection
Tell us the medium, pressure, flow rate, temperature and connection. Trinone Group receives the inquiry: version selection with the manufacturer, one contract and the documentation.